Home / Data center transformers
Guide · data centers

The data center transformer: four decisions that make all the difference

A 100 % electronic load, an absolute continuity requirement, a closed room: the data center combines everything that puts a generic transformer in difficulty. The right specification comes down to four decisions.

1 · Harmonics: size in K-factor

Servers, UPS systems and switch-mode power supplies massively distort the current. Those harmonics create extra losses, particularly in the windings and metal parts, that a classic "kVA" sizing ignores: a standard transformer loaded at 70 % can run as hot as at full load. The answer is a K-rated unit (commonly K-13 for a typical IT hall), designed to carry that spectrum without derating. The full reasoning is in the K-factor & harmonics guide.

2 · Redundancy: transformers that live at half load

In an N+1 or 2N architecture, each supply chain must be able to pick up the other's load: in normal operation every transformer therefore runs around 40–50 % of its rating. The direct design consequence: no-load losses (P₀), paid 24/7, weigh proportionally more than load losses. A unit optimised for low no-load losses (up to and including an amorphous core) pays back all the faster when the PUE is watched closely.

Phased ramp-up. A data center fills in tranches, over years. Two healthy strategies: transformers per hall or tranche, added as deployment progresses; or an ONAN/ONAF unit (AN/AF in dry-type) whose fans unlock the phase-two rating, without oversizing from day one.

3 · Fire: F1 dry-type or ester, almost never mineral oil

In an occupied building, fire safety governs the technology choice. Two routes: the cast resin dry-type transformer (fire behaviour class F1: self-extinguishing, limited smoke), the standard for indoor electrical rooms; or an ester-filled oil-immersed unit (K-class fluid, fire point above 300 °C) when you want the advantages of a liquid. Mineral oil, for its part, stays outside.

4 · Supervision: the transformer joins the DCIM

A data center measures everything; the transformer is no exception. On dry-type: PT100 probes per winding plus a temperature controller reporting over RS485/Modbus to the BMS/DCIM, with alarm and trip thresholds. On oil-immersed: a DGPT2 relay wired to the protection. These options appear as such in the "Protections / accessories" field of our configurator.

Grid side: the MV connection

From a few hundred kW, the supply runs through an MV delivery substation (in France under NF C 13-100, with the connection processed by the DSO), often a compact prefabricated substation to control schedule and footprint. Power, number of transformers and growth path are set with the design office at sketch stage: the moment when everything is still simple.

General design pointers; the exact K class, technology and architecture are determined with your design office from the real IT load and the site's requirements.

Frequently asked

Dry-type or oil-immersed for a data center?

Indoors, cast resin F1 dry-type is the reference choice: no liquid, controlled fire behaviour. Ester-filled oil-immersed units have their case in a dedicated technical room or outdoors. Mineral oil stays in outdoor substations away from the building.

Which K-factor should I take?

K-13 covers most IT halls; a load that is very predominantly electronic can call for K-20. The right figure follows the actual harmonic spectrum (measurement or UPS data). State data center in the configurator and we set it together.

Why not simply oversize?

Because harmonics do not dilute proportionally, and a big under-loaded transformer pays high no-load losses around the clock. A suitable K rating, a right-sized power and, if useful, AN/AF for growth is more reliable and cheaper over time.

Two transformers at half load, is that not wasteful?

No: it is the price of availability in an N+1 or 2N architecture. The design adapts to it: low no-load losses weigh most at that operating point, which is precisely what we optimise for.

Go further

Ready to quote

Building or extending a hall? Let's size it.

Configure a quote →