Each sector has its constraints — density, bidirectional flow, fire safety, continuity. We design for them, not around them. Every application below maps to a field in our configurator.
100% electronic load and absolute continuity. K-rated designs for harmonics, redundancy running transformers at half-load (low no-load losses matter), F1 dry or ester for fire safety, and DCIM supervision (RS485/Modbus).
Step-up units feeding the grid: inverter voltages (400–800 V), double-secondary transformers, truly bidirectional flow, and evacuation substations up to HV.
Two fast-growing segments: BESS needs genuine bidirectional flow and K-rated design for PCS harmonics; EV hubs concentrate high power at one point, moving the connection to MV.
Robust units for demanding environments, MV connection via delivery substation, and DGPT2 protection — plus distribution and grid-connection transformers in volume.
Select your use case — the design integrates its constraints from the start.
Configure a quote →